What is a PICV and how does it work?

válvulas

Everything you need to know about the pressure-independent control valve.

By Fratelli Pettinaroli

A PICV, Pressure Independent Control Valve, is a valve that can be installed in chilled water heating and cooling systems to provide the following:
• Flow control: allows control of the modulation of heating/cooling outputs
• Flow regulation – allows flow rates to be set to specified design values
• Differential Pressure Control: Ensures constant differential pressure through the control valves, regardless of changes in pump speed or valve shut-off elsewhere in the system.

This means that each PICV performs the function of up to three different valves that would otherwise be necessary for the proper operation of a facility. These 3 valves would be the throttle valve, the two-way control valve, plus a differential pressure control valve.

PICVs are the best solution for flow control through air handling units, fan coil units, and chilled beams fed from variable flow heating and cooling systems. These are systems in which the pump speed and, in turn, the flow rate, vary in response to heating or cooling demand, resulting in savings in pump energy.

It is now very important to define with the utmost clarity how a PICV works.

Figures 1a and 1b show the typical simplified diagrams of the two most common types of PICV.


Figure 1a. Three-section IPCP.


Figure 1b. Two-section LCCP

Some valves, as shown in Figure 1a, are made up of three distinct sections that correspond to the different functions of the valve, i.e., pressure regulation, flow adjustment, and modulating flow control. There is also the option for the flow adjustment and flow control functions to be combined within the same valve section as shown in Figure 1b.

Each section of the valve works as follows: the inlet to the valve houses the differential pressure regulator. It features a flexible rubber diaphragm that flexes against a spring that simultaneously varies the size of the opening for the passage of flow. One side of the diaphragm is in contact with water from the inlet to the valve at a pressure P1, while the other side is in contact with water from the outlet to the valve at a pressure P4.

This means that if there is any change in the differential pressure in a range from P1 to P4, the position of the differential pressure regulator will also change. The result will be that the differential pressure P2 to P4 (i.e., downstream of the differential pressure regulator at the valve outlet) will always remain constant regardless of changes in the overall differential pressure P1 to P4. Hence the term "pressure-independent": no matter how much external pressures vary, the performance and function of the valve will not be affected as long as it is within its working range. In the center section, there is a control valve to achieve the required design flow value, as specified by the manufacturer.


The required flow rate can be set using the flow setting dial built into the valve body. The stroke of the control valve is not affected by the flow adjustment. A full stroke provides good flow control, especially when using a modulation actuator. The control characteristic of a PICCV is not affected. If the flow adjustment device is combined with the modulation control valve (Figure 1b), as the flow setting is adjusted, part of the control valve travel is used to regulate the flow.

The reduction in stroke affects modulation flow control through the remaining valve travel, once configured. Therefore, the control valve stroke available for modulation is limited. This limitation in modulation could affect the performance of the valve and end up converting the valve to an ON-OFF type.

Pressure taps built into the valve allow the overall pressure differential P1 to P4 (or P3) to be measured to ensure that the valve is operating within the differential pressure range set by the manufacturer. Careful evaluation will be necessary whenever static balancing (DRV and commissioning sets) and IPCP (dynamic balancing) are desired in the same system. A system where the terminal units are equipped with static balancing without dynamic protection will only have a full design flow during commissioning and the flow will change under load conditions.

At the outlet to the valve body there is a flow adjustment device. This allows the valve to be set to partial. This can lead to excess flow through the DRV and reduced system pressure, which would result in an impact on the performance of the PICV (low start-up). In other words, there will be an effect on the overall performance of the system.

The performance of PICVs makes them ideal for use in variable flow systems.

Any changes in P1 pressure (such as those that could be caused by changes in pump speed or by valve shut-off in other parts of the system) will be automatically compensated for by the action of the differential pressure regulator. The controller will simply increase the resistance of the valve if P1 increases or decrease it if P1 decreases.



In addition, the regulator's ability to maintain a constant pressure differential between P2 and P3 has two important implications. First, with the control valve fully open and the flow adjustment device set to its required value, the valve effectively becomes a constant flow regulator (since a constant pressure differential through a constant resistor will result in a constant flow rate).

Therefore, if installed without the actuator, the valve can be used as a flow limiting valve, to keep the flow at a fixed preset value, regardless of changes in other parts of the system. This can be useful in by-pass circuits.

Second, by maintaining a constant pressure differential across the control valve and flow adjustment device, the authority of the control valve is maximized. The authority of a valve is an indication of how accurately the valve will be able to modulate flow when opened and closed. To achieve a correct level of authority, the pressure differential across the valve must be at least 50% of the total pressure differential in the pipe, branch, or circuit for which you are controlling the flow.

Such a valve would be considered to have an authority of 0.5. It is often impossible to size conventional 2-way control valves with such a high level of authority, because the controlled circuit can include the terminal unit and pipe losses to a remote pump or DPCV. In many applications, this condition requires 2-way valves with too high resistances. In this way, the most common authority value of valves is usually 0.2, which is a figure that is far from ideal.

In a PICV, the level of authority is improved because the differential pressure P2 to P3 (or P1 to P2) through the control valve and the flow adjustment device is effectively the circuit by which the valve controls the flow. This means that there is no need to take into account the pressure loss of the terminal unit and piping for valve selection, and valves can be selected based on flow rate only.

Duván Chaverra Agudelo
Duván Chaverra AgudeloEmail: [email protected]
Jefe Editorial en Latin Press, Inc,.
Comunicador Social y Periodista con experiencia de más de 16 años en medios de comunicación. Apasionado por la tecnología y por esta industria.

4 comments

• If you're already registered, please log in first. Your email will not be published.
  • Me parece muy interesante la aplicación que se le puede dar a este tipo de válvulas de balance hidráulico, en sistemas industriales con tramos largos de tuberías adonde es requisito controlar la distribución adecuada de fluido refrigerante, como por ejemplo en intercambiadores de calor, tanques con chaquetas de enfriamiento o calentamiento. Gracias por el aporte.

Leave your comment

In reply to Some User
Climate comfort meets efficiency and environmental sustainability in a Caribbean mall

Climate comfort meets efficiency and environmental sustainability in a Caribbean mall

Colombia. It recently began the installation of a modern air conditioning system, parking lot ventilation and solar energy in the Buenavista Shopping Center, in the city of Barranquilla.

AHRI Latam announces LBNL call for Mexican HVAC manufacturers

AHRI Latam announces LBNL call for Mexican HVAC manufacturers

Mexico. Lawrence Berkeley National Laboratory (LBNL) is leading an initiative to evaluate opportunities for the advancement of energy-efficient cooling technologies in the country.

Mitsubishi Electric and AWS sign memorandum of understanding

Mitsubishi Electric and AWS sign memorandum of understanding

International. In this way, Mitsubishi Electric Corporation and Amazon Web Services (AWS) will work together in cloud services and data centers.

Advansor to launch a plug-and-play reversible CO2 heat pump

Advansor to launch a plug-and-play reversible CO2 heat pump

International. Advansor's new solution seeks to position itself as a sustainable alternative to heating systems based on fossil fuels.

Emergent Cold LatAm obtains sustainable certification in Central America

Emergent Cold LatAm obtains sustainable certification in Central America

Guatemala. Emergent Cold Latin America has obtained a new EDGE Advanced certification for sustainable construction, this time for its unit in the Guatemalan town of Palín.

Reliable Controls launches new controller for automation systems

Reliable Controls launches new controller for automation systems

International. The company Reliable Controls has specified that it is the MS/TP model corresponding to its RC-FLEXone BACnet building controller.

Air conditioning for cancer patients: a success story

Air conditioning for cancer patients: a success story

Mexico. The optimization of air conditioning systems in a hospital has become a crucial factor for the well-being of patients and medical staff.

Vertiv and Compass Datacenter develop combined air and liquid cooling system

Vertiv and Compass Datacenter develop combined air and liquid cooling system

International. Vertiv and Compass Datacenters announced a collaboration to develop the first-of-its-kind solution that will facilitate future AI deployments.

Thermostats for BACnet networks

Thermostats for BACnet networks

Contemporary ControlsThe BASstat series of communicating thermostats produced by Contemporary Controls provides seamless integration into BACnet/IP (Wi-Fi) or BACnet MS/TP (EIA-485) networks.

Condensate pumps

Condensate pumps

HartellPlenum-rated condensate pumps are a Hartell solution for ventilation areas and air distribution chambers, backed by decades of proven performance. In addition, these pumps improve the safety...

Free Subscription
SUBSCRIBE TO OUR NEWSLETTER
DO YOU NEED A SERVICE OR PRODUCT QUOTE?
LASTEST INTERVIEWS
SITE SPONSORS










LASTEST NEWSLETTER
Ultimo Info-Boletin