Fault detection and solution in thermal expansion valves

The following text will discuss the correct way to diagnose and troubleshoot a thermal expansion valve (TXV) system for flow control. By: Al Maier*
 

With the emergence of the minimum 13 SEER standard in January 2007, virtually all residential split air conditioning manufacturers stopped designing equipment with flow meters and instead used thermal expansion valves (TXV, to regulate the rate of refrigerant feeding the evaporator. TXV valves make it possible for the system to use energy more efficiently by keeping the evaporator closer to the optimal superheat level in all operating conditions. In addition, it allows the system a rapid decrease in suction pressure under optimal conditions after a shutdown cycle. Operation and operation of TXV valves Although TXV valves offer many operational advantages, those unfamiliar with them consider them a mysterious device and end up replacing them unnecessarily. The TXV valve has a single function: to control the flow of coolant passing to the evaporator in an exact proportion to the evaporation rate of the refrigerant in the evaporator. By responding to the temperature of the refrigerant gas leaving the evaporator and the pressure of the evaporator, the TXV valve can control the gas leaving the evaporator at a predetermined superheater. Superheat is the temperature of a vapor that is above its saturation temperature. It is calculated by measuring the actual temperature of the evaporator outlet and subtracting the temperature corresponding to the evaporation pressure. To locate faults in a TXV  valve it is important to first understand how it works. There are three forces that determine the operation of a TXV valve. P1, i.e. the pressure created by the remote bulb; P2, the pressure of the evaporator or equalizer, and P3, the equivalent pressure of the superheat spring. The pressure of the remote bulb (P1) corresponds to the cooling temperature coming out of the evaporator. When this pressure increases, the valve needle tends to the "open" position. Opposed to this force, influencing the lower part of the diaphragm and moving the needle in a "close" direction, is the force exerted by the pressure of the evaporator and that exerted by the superheater spring. The valve will assume a stable position when these forces are in equilibrium (P1=P2+P3). When the temperature of the refrigerant leaving the evaporator rises above its saturation temperature—corresponding to the pressure of the evaporator—the pressure in the remote bulb increases, causing the valve needle to move in the "open" direction. Conversely, when the temperature of the refrigerant gas leaving the evaporator decreases, the pressure in the remote bulb becomes lower and the valve needle moves in the "close" direction. The factory adjustment of the TXV valve superheater is done with the needle starting to lift from the seat. An increase in the superheater is necessary for the valve to open to its sorting position. This is an important concept, as it means that a valve with a factory setting of 8° will not maintain an 8° superheater  at a maximum load. An additional superheater is necessary to make the valve "rub" its sorting ability.

Detection and solution of faults in TXV valves

There are three main failure modes in a TXV valve. The valve may be feeding too much coolant (supercharging); may not be feeding enough refrigerant (underfeeding); or it may alternate from feeding too much to too little (fluctuation). Below we will discuss each of these flaws in detail:

- Publicidad -

Overfeeding It occurs when the amount of refrigerant feeding to the evaporator is greater than what can be evaporated, causing the coolant to be returned to the compressor.  Overcharging symptoms include frosting of the compressor cover, noise emission in the compressor, low superheat in the evaporator, and normal or above normal suction pressures. Flooding may be due to any of the following causes: • Inefficient or smaller than normal compressor: if the compressor capacity is low, the suction pressure will be higher than normal and the superheater will be low. If you suspect this is the problem check with the compressor manufacturer. • Low superheat adjustment: In external adjustment valves, turn the stem clockwise to increase the superheat. • Moisture: Any water residue in the system can freeze on the TXV valve, preventing it from working properly. If you think this is the case, install a good filter dryer for the liquid line. It is also advisable to install a humidity indicator for the liquid line that allows the technician to monitor the humidity level of the operating system. • Dirt or debris: any foreign material that manages to pass the inlet filter can get lodged between the needle and the port of the TXV valve, preventing it from closing properly. Again, the recommendation is to install a filter dryer in the system to prevent the circulation of dirt and debris that can cause failures in the operation of the system. • TXV valve seat drip: If the needle  and port are not properly seated, liquid coolant will flow through the valve, which should not happen. When checking the valve, impurities and debris may appear. If so, the TXV valve can be cleaned and put back into operation. If inspecting the valve shows damage to the needle or port caused by wire drawing or erosion of the needle, the valve should be replaced. • Larger than normal valve: Make sure that the valve specified by the equipment manufacturer has been installed in the system. A valve too large for the capacity of the system will tend to overfeed. • Incorrect position of the bulb: ideally, the bulb of the power element is located in a horizontal section of the suction line - immediately after the evaporator outlet. It should be very close to the equalizer connection, but upstream. The bulb must be firmly attached to the suction line to maintain good thermal contact. In addition, the bulb should not receive external sources of heat.
______________________________________________________________________

Box To calculate the superheat:

  • Determine the suction pressure at the evaporator outlet.
  • Use a pressure/temperature table for the appropriate refrigerant and determine the saturation temperature corresponding to the pressure measured in step 1.
  • Measure the temperature of the suction line at the location where the remote bulb is located.
  • Subtract the saturation temperature you set in step 2 to the measured temperature in step 3. The resulting difference is the superheater.

Superheater adjustment for external adjustment TXV valves only:

  • Remove the seat cover from the bottom of the valve, leaving the adjustment stem exposed.
  • Turn the stem clockwise to increase the superheater – decrease the flow of the coolant.
  • Turn  the stem counterclockwise to decrease the superheater – the flow of the coolant increases.

*Al Maier is vice president of application engineering at Emerson Climate Technologies Flow Control Division. For more information, call: 314-569-4680 or email: [email protected].
 

 

 

2 comments

• If you're already registered, please log in first. Your email will not be published.
  • El equipo marca la falla "flujo bajo en succion". Y dice que una de las posibles fallas es la txv. Como lo compruebo?

Comments are closed

The comments for this content are closed.

AHR Expo Orlando sets record numbers by surpassing 50,000 attendees

AHR Expo Orlando sets record numbers by surpassing 50,000 attendees

International. The AHR Expo took over Orlando for a week characterized by its agile pace of learning, reconnection, analysis and demonstration of all the novelties that are coming to the HVAC-R...

A refrigeration solution proves its effectiveness in the logistics sector

A refrigeration solution proves its effectiveness in the logistics sector

International. In the logistics sector, efficient refrigeration is no longer just a requirement but a matter of safety, quality and performance.

Pharmaceutical cold chain: a model for efficient logistics in other industries

Pharmaceutical cold chain: a model for efficient logistics in other industries

International. The company Kryotec has highlighted that innovations in the pharmaceutical cold chain optimize traceability, monitoring and costs, guaranteeing safety and regulatory compliance in...

Samsung Mexico inaugurates first training center specialized in air conditioning systems

Samsung Mexico inaugurates first training center specialized in air conditioning systems

Mexico. Samsung opened this space for customers, employees and business partners, aimed at training, service and support, while strengthening the knowledge of professionals in air conditioning...

Eurovent updates its Recommendation for evaporative cooling equipment

Eurovent updates its Recommendation for evaporative cooling equipment

International. Eurovent has published a second version of its Recommendation 9/12 on the performance efficiency standard for evaporative cooling equipment.

Hisense showcased its new generation of HVAC solutions at AHR Expo 2025

Hisense showcased its new generation of HVAC solutions at AHR Expo 2025

International. Hisense Comfort showcased energy-efficient climate solutions designed to meet the changing demands of residential and commercial customers in Orlando, Florida.

Pettinaroli kicked off his Roadshow Colombia

Pettinaroli kicked off his Roadshow Colombia

Colombia. The city of Medellín was the first stop of the Pettinaroli Roadshow Colombia, a tour carried out by the Italian manufacturer to present its novelties for energy measurement in HVAC...

Sodeca reported that it is generating a third of the energy it consumes

Sodeca reported that it is generating a third of the energy it consumes

International. Sodeca Group announced that it continues to strengthen its sustainability and energy efficiency, thanks to which it already has more than 1,000 solar panels located on the roof of its...

Innovair opens new digital channels for Latin American markets

Innovair opens new digital channels for Latin American markets

Latin America. Innovair Corporation, a manufacturer of air conditioning and refrigeration equipment, announced the launch of its new pages on the social networks Facebook and LinkedIn.

Copper Group introduced a new line of refrigeration equipment to the Costa Rican market

Copper Group introduced a new line of refrigeration equipment to the Costa Rican market

Costa Rica. Copper Group launched its new line of refrigeration evaporators and condensers in Costa Rica, under the Adina Winter brand.

Free Subscription
SUBSCRIBE TO OUR NEWSLETTER
DO YOU NEED A SERVICE OR PRODUCT QUOTE?
LASTEST INTERVIEWS
SITE SPONSORS










LASTEST NEWSLETTER
Ultimo Info-Boletin