Control valves in hydraulic systems (II)

altIn this second part we continue to analyze some of the assumptions that applications use to model the hydraulic system and the electrical consumption of pumps. by Julio Londoño*


After observing in the first part of this article how control valves work by means of a modeling to obtain significant savings in hydraulic air conditioning systems, we will continue to analyze some technical aspects such as the creation of new curves for the distribution bmba. Create new curves for the distribution pump: In order to create a new curve for the pump, a new group of assumptions must be established that allow us to calculate the excess flow generated by the pressure-dependent valves. The following methodology is based on an article written by Mack Wallace for ASHRAE (McHenry Wallace Jr. PE, A New Approach to Modeling Pressure Dependent Control Valves published by ASHRAE, white paper). New Assumption-1
The pressure through the valve fluctuates between 5-10 psi: Using the behavior area of the pump head (shown in Figure 2 in the previous article) and starting from the fact that you have a well-balanced system with well-selected valves we assume that these are normally subjected to pressure fluctuations in the range of 5 to 10 psi. This assumption allows us to calculate the excess flow for each valve position.   To create the new pump curve we first calculate the flow values for each valve position at different differential pressures. Then to obtain the consumption of the pump in each position we use the affinity law of the pumps. New Assumption-2
The differential pressure through the valve has a normal distribution between 5-10 psi: To obtain the values of the pump consumption for each position of the valve we use a weighted average assuming a normal distribution of the differential pressure. In order to define the equations as a percentage, each average is then normalized against the values of a specific valve. alt The curve of the weighted averages is plotted in a spreadsheet and with the graphical tools you can find the equations of the graph and the coefficients of each variable. These coefficients are entered into the configuration of the pump curve according to the requirements of each modeling package. For example, Trane's Trace 700 uses a fourth-degree polynomial curve, and DOE's eQuest uses a quadratic equation.alt alt  


Using the new curves
We set up a new pump in eQuest and Trace 700 using the coefficients given in the graphs. We then compared the results using a model of a typical five-story office building in Chicago, with an area of 750,000 sq.ft. The cooling system is of the decoupled type, also called primary/secondary, with two water-cooled chillers, of 1,000 tons each, with dedicated constant volume pumps for each cooler and a variable volume pump for distribution. These were the results: Using Trace 700:
Figure 13 alt Using eQuest:
Figure 14 alt In each case the building was modeled using as a basis the basic curves included in each package, this option corresponds to ideal conditions in the hydraulic system when installing independent pressure valves. The building was then modeled using the new curves to obtain electricity consumption using pressure-dependent valves. In both cases, an increase in the consumption of the distribution pumps of around 35% was obtained. This value is very close to the values that have been obtained in real systems when valve retrofits are made and conventional valves are replaced by pressure independent valves. This value varies depending on the type of building, its construction and its geographical location. Conclusions
It is important to recognize that this method is very conservative and is more appropriate for new building designs, because in existing buildings it is possible that the valves can see greater pressure fluctuations, leading to much larger savings. The reasons for these wider pressure fluctuations are manifold, some may be that the building is not well balanced, that the control valves have not been properly selected or that the coils no longer offer the same original heat exchange. This model also does not include the inefficiencies caused in the cooling plant due to poor heat exchange in the coils and low delta T syndrome. That is why it is very important that the engineer in charge of modeling knows the impact on energy efficiency according to the type of valves installed and the current conditions of the building. *Julio Londoño is the Product Manager of Belimo more information in [email protected]

No comments

• If you're already registered, please log in first. Your email will not be published.

Leave your comment

In reply to Some User
Mirage and Conalep Navojoa promote the training of refrigeration and air conditioning technicians

Mirage and Conalep Navojoa promote the training of refrigeration and air conditioning technicians

Mexico. Mirage announced a strategic alliance with the Plantel Conalep Sonora Navojoa to strengthen the training of new technicians in the sector.

New commitment to thermoacoustics for more efficient heat pumps

New commitment to thermoacoustics for more efficient heat pumps

United States. Copeland has invested in BlueHeart Energy, a Dutch startup developing thermoacoustic technology for more efficient and sustainable heat pumps.

Reliable Controls Appoints Sean Roukey as Business Development Executive

Reliable Controls Appoints Sean Roukey as Business Development Executive

International. Reliable Controls has appointed Sean Roukey as its new Business Development Executive for the Northeast United States.

KNX LATAM revolutionizes automation in Latin America with the Virtual Building Automation Days

KNX LATAM revolutionizes automation in Latin America with the Virtual Building Automation Days

Chile. Next Thursday, April 10th, KNX Latin America will hold the Virtual Building Automation Days, registration is free of charge.

GreenYellow and La Fazenda inaugurate a sustainable refrigeration system

GreenYellow and La Fazenda inaugurate a sustainable refrigeration system

Colombia. A new energy-efficient refrigeration system was installed at the La Fazenda refrigeration plant in Puerto Gaitán, Meta.

Officine Mario Dorin announces ambitious expansion plan at its Florence headquarters

Officine Mario Dorin announces ambitious expansion plan at its Florence headquarters

International. Officine Mario Dorin, a refrigeration company, has announced a major expansion plan at its headquarters in Florence, Italy.

Copeland expands its presence in Latin America with a new office in Chile

Copeland expands its presence in Latin America with a new office in Chile

Chile. As part of its regional growth strategy, Copeland has opened a new office in Santiago, Chile, strengthening its presence in the HVACR market.

Environment and UNDP recognize ten women for their contribution to the protection of the ozone layer

Environment and UNDP recognize ten women for their contribution to the protection of the ozone layer

Dominican Republic. Within the framework of International Women's Day, the Ministry of Environment and Natural Resources and the United Nations Development Program (UNDP) highlighted the work of ten...

Register for the Building Automation Webinar: Keys to Understanding Modbus and BACnet

Register for the Building Automation Webinar: Keys to Understanding Modbus and BACnet

International.  On March 27, 2025, ACR Latin America will offer a webinar focused on building automation protocols, with an emphasis on understanding Modbus and BACnet.

Scientists develop the first elastocaloric air conditioner on a commercial scale

Scientists develop the first elastocaloric air conditioner on a commercial scale

International. Researchers at the Hong Kong University of Science and Technology (HKUST) have developed the first elastocaloric air conditioning system with cooling capacity on a commercial scale.

Free Subscription
Remember Me
SUBSCRIBE TO OUR NEWSLETTER
DO YOU NEED A SERVICE OR PRODUCT QUOTE?
LASTEST INTERVIEWS
SITE SPONSORS










LASTEST NEWSLETTER
Ultimo Info-Boletin